Working principles of SF6 gas density table
1. When the density meter is not installed, if the ambient temperature is 20 ℃, the pointer 2 points to 0MP, but if the ambient temperature is not 20 ℃, because the double-layer metal belt 3 is in accordance with the ambient temperature and 20 ℃ difference to compensate So that when the ambient temperature is higher than 20 ° C, the double-layer metal strip 3 is elongated and its lower end is displaced in the direction of 5, causing the gear mechanism and the pointer 2 to move in the direction in which the density or pressure indication value decreases, The reading of the pointer 2 is greater than 0MP; otherwise, when the ambient temperature is below 20 ° C, the gear mechanism and the pointer 2 will move in the direction of increasing the density or pressure indication value. 2. When the SF6 gas is charged to the circuit breaker , the end of the elastic metal pipe 1 is displaced in the direction of 4 as the gas pressure is gradually increased, and the double-layer metal strip...